Temporary prefabricated post-disaster shelters suffer from severe energy loss and poor indoor thermal stability during cold seasons due to low thermal mass and lightweight envelopes. In this study, an integrated low-temperature hydronic underfloor heating system coupled with flat-plate solar collectors and an auxiliary gas boiler is designed and evaluated to ensure thermal comfort and reduce fossil fuel reliance. The transient thermal behavior and energy balances were modeled through dynamic building energy simulation (using the EnergyPlus simulation engine) over a full annual cycle, validated against benchmark TRNSYS models. The proposed system was comparatively analyzed against a conventional boiler-radiator configuration across three distinct climate zones: cold (Tabriz), semi-arid moderate (Tehran), and hot-arid (Yazd). The results demonstrate that the solar-assisted radiant floor system successfully stabilizes indoor temperatures within the comfort range of 20–22 °C during extreme winter periods. Furthermore, compared to traditional radiator heating, the system achieves annual fuel savings of 32.3%, 29.5%, and 27.8%, while reducing annual CO2 emissions by 20%, 14%, and 15% in Tabriz, Yazd, and Tehran, respectively, highlighting its superior performance in cold climates with intense heating loads.